B
16
Manual model IndAC
2.10 Switching on and
checking operation
For all units:
1 Check the following connections:
- power supply;
- cabling between control unit and
units, and between the different
units;
- external control components (if any).
2 Switch the mains supply on.
3 Switch the air curtain on using the control
unit, and check if the air curtain blows
out air.
c
Caution:
If the fans run out of true, the unit may
not be standing or hanging completely
level. Correct this where necessary.
4 Check the direction of rotation of the
fans.
Wrong: the blades go
forward
Correct: the blades go
backward
If necessary, correct the direction of
rotation by interchanging the connections
of two phases from the mains supply.
For water-heated units:
5 Check if the heat exchanger is
connected correctly.
6 Make sure the CH system is turned on.
7 Feel whether the discharged air gets
warm.
8 Vent the heat exchanger, if necessary.
For units with electric heating:
9 Set the isolating switches on all units to
position 1.
10 Switch the air curtain on using the control
unit.
11 Feel if the discharged air gets warm.
Commentaires sur ces manuels