Manual model IndAC
3.2.2 Heating element
For water-heated units:
1 Remove inlet grille 1.
For units with electric heating:
1 Set the isolating switch 1 on the unit to
the zero position.
2 Remove the cover 2.
3 Remove the inlet grille 3.
4 Remove the cover from the cable
compartment 4.
3.3 Cleaning
You can clean the unit's interior and exterior
with water and a domestic cleaning agent.
Do not use any solvents.
The fans can be cleaned with water as well.
The unit has holes for the discharge of water.
w
Warning:
Do not spray water on the fans and
terminal boxes.
Carefully remove dust from the heating
element with a vacuum cleaner.
d
Danger:
Do not clean electrically-heated units with
water.
3.4 Scheduled maintenance
3.4.1 Monthly maintenance
- Check the heating elements and the fans
for dust and other contaminants. Clean if
necessary.
- Check if all fans are working.
- Check if the air curtain is working at all
control unit settings.
- Check the discharge section for
contaminations and/or blockages; clean
if necessary.
For units with water heating:
- Check for water leaks. If there is a leak,
disconnect the unit from the mains, and
repair the leak.
- Check if the water circuit contains any
entrapped air. Bleed if necessary.
Vue de la page 17